Cassette Fan Coil Unit

  • Brand:Tili
  • Refrigerant:R410A
  • Voltage:220-240V/50Hz
  • Capacity:12HP-15HP

The ceiling-mounted central air conditioners use artistic panels and have uniform dimensional design at four sides. The installation layout is convenient and flexible. The air conditioners supply strong and even circular air through wideangle air outlets from four sides, quickly providing a comfortable indoor environment. In addition, advanced air circulation design continuously introduces fresh air from outside to build a natural and healthy living environment. This series is ideal for office buildings and malls, meeting requirements for comfortable environment in modern apartments and office buildings.

Model No.Indoor unitEKCK030AEKCK050A
Outdoor unitEKAA030AKEKAA030ARKEKAA050AKEKAA050ARK
Nominal Cooling CapacityW780078001250012500
Nominal Heating CapacityW.--8000.--15000
Rated input power CoolingW2550260043004300
HeatingW.--2500.--5100
Rated currentCoolingA12127.67.6
HeatingA.--11.5.--9.1
EERW/W2.822.772.792.79
Energy Efficiency Rating
3444
Indoor unitAir flowm³/h1200120017001700
PowerW127186
CurrentA0.580.86
NoisedB(A)4044
Main unit                (L * W*H)mm 705*705*290832*832*290
Panel                       (L * W*H)mm 830*830*30980*980*30
Weightkg3141
Outdoor unitNoisedB(A)5961
Weightkg5556105112
L * W*Hmm 840*311*697970*345*1255
Power supply
220v /50hz380v/50hz
Connector sizeExternal diameter of liquid tubemm(in.)9.52 (3/8)
External diameter of air tubemm(in.)15.88 (5/8)19.05 (3/4)
Pipe connection mode
The copper tube tulip opening is connected to the threading connector
Water drainage pipe
diameter 27mm
Note:
1. The GB 19576-2004 EER standard is applied.
2. The nominal cooling capacity is measured under the following conditions: The indoor dry/wet bulb reads 27/19 °C and the outdoor dry/wet
bulb reads 35/24 °C.
3. The nominal heating capacity is measured under the following conditions: The indoor dry/wet bulb reads 20/15 °C and the outdoor dry/wet
bulb reads 7/6 °C.
4. The sound pressure level noise is measured through test in a semi-anechoic room. Due to environment noise and other factors in actual
operation, the actual noise may be different from those listed in the preceding table.
5. The preceding data shows parameters when the horizontal length of connecting pipes between indoor and outdoor units is 5 m.
6. For details about on-site power distribution and wiring for unit installation, see the nameplate or installation manual of the unit.

Electric parameter
ModelIndoor unitEKCK030AEKCK050A
Outdoor unitEKAA030AKEKAA030ARKEKAA050AKEKAA050ARK
Power supply220v/50hz380v/50hz
Power cableCross sectional area (mm²)4444
Number3355
Cables connecting indoor unit and outdoor unitCross sectional area (mm²)2.52.52.52.5
Number5656
Fault reporting cables between indoor and outdoor unitsCross sectional area (mm²)1.51.51.51.5
Number3333
Note:
1. The preceding cable specifications are recommended.
2. All wires must be well connected. Connecting wires must be fixed by wire clips.
3. All wires must avoid refrigerant pipeline and movable parts such as compressor and fan motor.
4. Connecting wires must adopt chloroprene rubber copper conductor cables. The cross sectional area must meet the requirements listed on
the preceding table.
5. A circuit breaker with sufficient capacity must be set at the power input wire. The breaker has a contact separation of at least 3 mm.
6. For details about on-site power distribution and wiring for unit installation, see the nameplate or installation manual of the unit.